Tangit FP 550 2-C Fire Protection Foam

Features and Benefits

  • For fire-resistant and smoke-tight sealing of pipe, cables and cable trays as well as mixed penetrations.
  • For openings from 50 x 25 to 35 x 35 cm resp. 35 cm diameter.
  • Very well suited for acoustic and thermal insulation.

Product Advantages

  • Very fast installation of medium-sizes bulkheads with multiple penetrations (up to 60% faster tested by REFA time efficiency study).
  • Even suitable for first-time users after prior instruction.
  • Also suited for lightweight partition walls from 10 cm wall thickness upwards.
  • Fire-resistant and smoke-tight for at least 90 minutes.
  • Self-expanding for sealing most different cable/pipe ducts regardless of the penetration shape.
  • Flexible and uncomplicated later installation of cables and pipes.
  • Excellent, cost-saving foam yield of approx. 3.5 liters per cartridge.
  • Rapid curing: cuttable after approx. 4 minutes, final strength after approx. 20 minutes.
  • Meets the requirements of DIN 4102 and MLAR 2005/LAR/RbALei.
  • Future-proof due to compliance with the European standard EN 1366.
  • Hardly inflammable acc. to DIN 4102 (B1).

 

Packaging Details

  • 300ml Cartridge

Intended
Use

 

  • For fire-resistant and smoke-tight sealing of pipe, cables and cable trays as well as mixed penetrations. Also, for openings up to 50 x 25 to 35 x 35 cm resp. 35 cm diameter and well suited for acoustic and thermal insulation.
  • Required amount: Approx. 6 cartridges are required for an empty bulkhead of 35 x 35 cm.

 

Please note:

  • Tangit FP 800 Fire Protection Coating is a required system component for use in conjunction with Tangit FP 550 Fire Protection Foam.
  • Fire-resistant penetrations must be equipped with an identification plate.
  • Please also refer to our Technical Approvals, Technical Data Sheet and Safety Data Sheet.

Applications  

Step 1

The substrate must be clean and dust-free.

Step 2

Discard the pre-foam (approx. 3 squeezes) until the material is completely mixed.

Step 3

The foam is cuttable after only approx. 4 minutes.

Step 4

After cleaning the opening, the cartridge can be closed again.

Step 5

Spare mixers are available (Tangit FP 504 mixers).

Step 6

Please refer to our "Tangit Fire Protection Handbook" for detailed application information.